Products Types of Insulation Temp Rating °C Size Range Insulation Build Grade Properties of Insulation Main Applications Specifications
Paper Covered/ Lapped Wire Multi Lapped Manila/ Kraft Paper or Crepe Covering Butt Lap, Half lap wound and Multi layers 105-A 6.4 to 0.50 mm 0.05 to 0.125 mm Kraft Paper thickness or as required High dielectric strength when oil immersed. Uniform radial Separation, Mechanical resistance Distribution transformers, ESP and welding transformers IS: 7404 Pt-1, BS: 4653: Pt-2, BS: 6811 Section 8,1 IEC: 317-27
Paper Covered/ Lapped Strips Multi Lapped Manila/ Kraft Paper or Crepe Covering Butt Lap, Half lap wound and Multi layers 105-A upto 100 Sq. mm 0.05 to 0.125 mm Kraft Paper thickness or as required High dielectric strength when oil immersed. Uniform radial Separation, Mechanical resistance Oil filled distribution and power transformers. IS: 7404 Pt-2, BS: 4653 Pt-2, IEC: 317-27
Nomex (Meta Aramid paper) Covered/Lapped Wires Aromatic Polyamide Fibre Based Paper Covering Butt Lap, half Lap, Multi layer 220-C 6.4 to 0.50 mm 0.05 to 0.125 mm High mechanical and electrical strength. Lapped construction gives uniform covering. Exceptional thermal rating. High performance coils. Dry type and resin cast transformers. IS: 11174, BS: 4653 Pt-2, IEC: 851

Get In Touch

We would love to hear from you! Please fill out this form and we will get in touch with you shortly.
  • This field is for validation purposes and should be left unchanged.

“Copyright © 2016 DuPont. All rights reserved. The DuPont Oval Logo, DuPont™, The miracles of science™ and all products denoted with ® or ™ are trademarks or registered trademarks of E. I. du Pont de Nemours and Company or its affiliates”

DISCLAIMER: The technical information contained herein is the result of extensive testing in the manufacturer’s laboratories. In addition any application advice given verbally, in writing or by testing corresponds to the best of our knowledge and belief. Since the use and application of any of our products lies beyond our area of control, it remains the responsibility of the user to verify the product’s suitability for their application.

Back to Top